Compressed Air Solutions
  • Screw Air Compressor
  • Oil Free Compressor
  • Diesel Portable Compressor
  • Gas Compressor
  • Specialty Compressor
  • Air Treatment
ISO 9001 Certified
24-Month Warranty
OEM & ODM Support
Factory Direct Price
Get Custom Quote →
Compressed Air Demand Calculation
Technical Guide

Compressed Air Demand Calculation

Technical Article
10 min read
System Sizing

Calculation Formula and Variables

Q_total = Σ(Qi × ni × Ki) × Ks × Kf

Q_total is total system air demand, in CFM. Qi is air consumption per unit for a certain equipment type, ni is the number of units. The three coefficients Ki, Ks, Kf respectively correct for equipment operating state, multi-equipment statistical characteristics, and pipe network losses.

The formula itself is simple. The hard part is getting the coefficient values right. Of the three coefficients, Ki takes the most effort. Ks and Kf are relatively fixed.

Equipment Utilization Factor Ki

The air consumption marked on equipment nameplates is the rated value. Ki converts it to the average value during production.

Continuous operation equipment is straightforward. Pneumatic conveying, pneumatic pumps, these things run non-stop once started. Ki is 0.9 to 1.0.

Intermittent operation equipment is where Ki calculation really matters. Reference values give 0.3 to 0.5, but this range is too wide. Directly applying it easily causes problems.

Here's a specific situation: a pneumatic clamp, 2-inch bore, 0.8-inch stroke, single action consumes about 0.0014 cubic feet (at 90 psi). If production cycle is 10 seconds, clamping and releasing once per cycle, that's 12 actions per minute, consuming about 0.017 CFM. But nameplate might say "air consumption 10 CFM." That's the theoretical value of the cylinder going full speed continuous reciprocation. Actual average consumption is only about 1% of nameplate value. Ki works out to only 0.016.

Of course most situations don't need this level of detail. But at least figure out equipment action frequency. Can't see "pneumatic clamp" and just fill in 0.4. Fast cycle production lines, Ki goes higher. Slow cycle, goes lower.

Air guns, pneumatic wrenches, these randomly used tools are even harder to estimate. Same air gun, different operators can vary consumption by double. Reference 0.1 to 0.3. Not sure, go high.

Ks and Kf

Simultaneity factor Ks addresses probability. Twenty-some pieces of equipment won't all hit max consumption at exactly the same time. More equipment, lower probability of simultaneous full load. Under 5 units: 0.9. 5 to 10 units: 0.8. 10 to 20 units: 0.75. Over 20 units: 0.7. These values apply to shops where equipment runs independently. If multiple machines are linked and move in sync, Ks needs to go higher.

Leakage and margin factor Kf compensates for pipe network leakage and expansion reserve. New systems leak 5% to 10%, old systems 15% to 25%. Kf ranges 1.1 to 1.3. New systems on the low side, old systems higher. Add more if expansion is planned. Don't make this coefficient too big. Oversized compressor selection leads to long-term low load operation, energy consumption actually goes up.

Calculation Example

A machining shop equipment list: CNC machining centers 4 units, each consuming 28 CFM, continuous operation. Pneumatic clamps 12 sets, each consuming 10 CFM, intermittent operation. Air guns 6 units, each consuming 18 CFM, random use.

CNC continuous operation, Ki at 0.95:
28 × 4 × 0.95 = 106.4 CFM

Pneumatic clamps intermittent, assuming medium cycle, Ki at 0.4:
10 × 12 × 0.4 = 48 CFM

Air guns random use, Ki at 0.2:
18 × 6 × 0.2 = 21.6 CFM

Three equipment types total 176 CFM.

Total 22 pieces of equipment, Ks from table is 0.7. New system with moderate expansion reserve, Kf at 1.2.

Q_total = 176 × 0.7 × 1.2 = 148 CFM
148 CFM
Calculated Demand
10-15%
Selection Margin
160-175 CFM
Compressor Size

Compressor selection adds 10% to 15% margin. Pick 160 to 175 CFM discharge capacity.

The pneumatic clamp Ki of 0.4 here is actually rough. For accurate calculation, need to know clamp action frequency. Assuming 15-second cycle, two actions per cycle, 0.002 cubic feet per action, about 0.014 CFM per minute. Ki is only 0.0013. But considering 12 clamp sets distributed at different stations with possibly different cycles, taking 0.4 across the board is conservative estimate. Better to have surplus than shortage.

Pressure Calculation

Air volume set, next is pressure.

P_source = P_end + ΔP_pipe + ΔP_dryer + ΔP_filter + ΔP_margin

P_end is end equipment required pressure. Look this up directly from equipment specs. The rest are losses along the way: pipe pressure drop 3 to 7 psi depending on diameter and length; dryer pressure drop 3 to 6 psi; filter pressure drop calculated for clogged element condition, 3 to 9 psi; safety margin 7 psi.

Compressed air system piping

That shop above, CNC needs 90 psi, pipe drop estimated 4 psi, dryer 4 psi, filter 6 psi, margin 7 psi:

P_source = 90 + 4 + 4 + 6 + 7 = 111 psi

Select 115 psi model.

Pipe pressure drop, for shops with short runs and reasonable diameter, taking 3 to 4 psi is fine. Runs over 600 feet or lots of branches and elbows, better to calculate separately. Simplified estimates easily cause insufficient end pressure.

Equipment consumption data, use manufacturer documents first. No documents, measure on site with flow meter. Spend more time analyzing process cycle for Ki values. More reliable than using reference values.

Footer Component - SOLLANT
滚动至顶部